Resolution - Manual - Modbus TCP Connector - Industrial Edge - Industrial Edge App - Modbus TCP Connector sends the tags from the PLC to the Databus or IIH in order to analyze and visualize the values of the Modbus TCP tags in apps such as Performance Insight. - Modbus TCP PLC - Modbus TCP Connector - Data transfer - Connectivity suite connector

Modbus TCP Connector

Portfolio
Industrial Edge
Product
Modbus TCP Connector
Software version
v4.2
Edition
04/2026
Language
English

NOTICE

Check the device's address map in the device manual before starting this procedure. This helps avoid unnecessary trial and error. It is not necessary to set "Bypass Optimization" to True for all tags with non-continuous addresses. Some devices can still read non-continuous tags in a single request. This behavior depends on the device's register memory map.

To bypass optimization for a tag, proceed as follows:

  1. In the tag configuration, set the "Bypass Optimization" option to True for the tag with the largest address.
  2. Deploy the configuration.
  3. Check if the error is resolved.
    • If the error is resolved, the procedure is complete.
    • If the error persists, set "Bypass Optimization" to True for the tag with the next largest address and repeat from step 2.