Common Configurator - Manual - SIMATIC S7 Connector - Industrial Edge - Industrial Edge App
SIMATIC S7 Connector
- Product
- SIMATIC S7 Connector
- Product Version
- v2.2.1
- Edition
- 08/2024
- Language
- en-US (original)
- You can only use one method of configuration, either Common Configurator or IEM. Configuring using the common configurator is the recommended way.
- Previous invalid characters such as
/
, #
, and \
are not supported in the Common Configurator. You must avoid configuring them.
- Char arrays are supported as individual elements in the IIH configurator. IEM users can still use them as individual elements with the data type chararray.
- New version of S7 Connector is compatible to work only with updated version of Common Configurator (V1.8.0).
- S7+ browsing in not supported with an Open Controller PC2 (CPU1515SP PC2).
- S7 connector tag read function does not work with S7-1200 PLC for Firmware versions below 3.0
- If the Excel sheet created by the TAG converter tool contains an array datatype, it is not supported after importing the file under a non-optimized connection.