Test results for 10K Tags - 40 connections - Manual - Connector for IEC 60870-5-104 - Industrial Edge - Industrial Edge App - Connector for IEC 60870-5-104 transfers data from IEC devices over TCP/IP network to the Databus or IIH, allowing the values of these tags to be analyzed and visualized in applications like Performance Insight. - Connectivity suite connector - Connector for IEC 60870-5-104 - Data transfer - IEC 60870-5-104 - International Electrotechnical Commission - TCP/IP network

Connector for IEC 60870-5-104

Product
Connector for IEC 60870-5-104
Product Version
v1.0.0
Edition
12/2024
Language
en-US (original)

Environment

  • Edge Device: SIMATIC IPC 427E
  • Databus version 3.0
  • Flow Creator
  • IEC 60870-5-104 Server Simulator (based on libiec60870-5-104)
  • Intel NUC (running IEC 60870-5-104 simulator)

Scenario

Parameter Details
Number of data sources 40
Tags per data source 250
Total tags 10,000
Information object type M_ME_S
Test duration 48 hours
Server speed (simulator) Data changes every 1-2 seconds

Result

  • CPU usage: 2-19% depending on server speed.
  • Memory consumption: 36 MB
  • Data loss: 0%
  • The IEC 60870-5-104 Connector maintained consistent data integrity with no observed data loss, even under a high load of 10,000 tags over 40 connections.