Supported data types - Manual - Connector for IEC 60870-5-104 - Industrial Edge - Industrial Edge App - Connector for IEC 60870-5-104 transfers data from IEC devices over TCP/IP network to the Databus or IIH, allowing the values of these tags to be analyzed and visualized in applications like Performance Insight. - Connectivity suite connector - Connector for IEC 60870-5-104 - Data transfer - IEC 60870-5-104 - International Electrotechnical Commission - TCP/IP network

Connector for IEC 60870-5-104

Product
Connector for IEC 60870-5-104
Product Version
v1.0.0
Edition
12/2024
Language
en-US (original)
Information Object Type Subtype Connectivity Suite data type Description
M_SP R.Value UInt8 unsigned integer, 1 byte
M_SP R.All Raw COT+SIQ+[timestamp]
M_DP R.Value UInt8 unsigned integer, 1 byte
M_DP R.All Raw COT+DIQ+[timestamp]
M_ST R.Value Int8 signed integer, 1 byte
M_ST R.All Raw COT+VTI+QDS+[timestamp]
M_BO R.Value UInt32 unsigned integer, 4 bytes
M_BO R.All Raw COT+BSI+QDS+[timestamp]
M_ME_N R.Value Float32 float, 4 bytes
M_ME_N R.All Raw COT+NVA+QDS+[timestamp]
M_ME_S R.Value Int16 signed integer, 2 bytes
M_ME_S R.All Raw COT+SVA+QDS+[timestamp]
M_ME_F R.Value Float32 float, 4 bytes
M_ME_F R.All Raw COT+ IEEE STD 754 + QDS+[timestamp]
M_IT R.Value Int32 signed integer, 4 byte
M_IT R.All Raw COT+BSR+[timestamp]
C_SC W[.Direct\|.Select][.SP\|.LP\|.P][.TS] UInt8 {0,1}
C_DC W[.Direct\|.Select][.SP\|.LP\|.P][.TS] UInt8 {0,1,2,3}
C_RC W[.Direct\|.Select][.SP\|.LP\|.P][.TS] Int8 {0,1,2,3}
C_SE_N W[.Direct\|.Select][.SP\|.LP\|.P][.TS] Float32 [-1, 1]
C_SE_S W[.Direct\|.Select][.TS] Int16 signed integer, 2 bytes
C_SE_F W[.Direct\|.Select][.TS] Float32 float, 4 bytes
C_BO W[.Direct\|.Select][.TS] UInt32 unsigned integer, 4 bytes